Description
Technical Specifications
- AC Input range : 160 V – 270 V
- Input Frequency : 47 Hz – 53 Hz
- Output Voltage : 230 V +/- 1%
- Output Frequency : 50 Hz +/- 0.5 Hz
- Waveform : Signwave
- Harmonic Distribution : <3%
- Invertor efficiency : >90%
- Power Factor : 0.8 logging to unity
- Overload : 110% for 5 minutes
- Crest Factor : 3:1
- Transient Recovery : within 3 Cycles
- Audible Noise : Less than 55 db upto 1 meter
Self & Diagnostics Features
An electronics circuit with digital logics continuously searches for the following faults and trips the system with audio-visual indications:
- Battery Over Voltage
- Battery Under Voltage
- Output AC Over Voltage
- Output Overload / short-Circuit
- Phase Fail for Three Phase models
Indicators
- Mains On
- Output On
- Inverter Overload
- Battery Low
- Output High Back Up
Ambient Conditions
Operating: 0°C – 45°C , Storage: 0°C – 60°C, Relative Humidity: 95% RH, Operating Altitude: upto 2000 meters.
Metering
Digital Metering for input voltage / output voltage frequency, output load, batteries percentage.
Features (optional)
Static By-Pass Switch, Serial RS 232 Inter face, Auto File Shutdown, Microprocessor based Digital Metering